homebridge-plc
v2.0.4
Published
Homebridge plugin for Siemens Step7 and compatible PLCs. (https://github.com/homebridge)
Downloads
345
Maintainers
Readme
homebridge-plc
Homebridge plugin for Siemens Step7 and compatible PLCs
SIEMENS S7 PLC plugin for Homebridge
- Uses snap7 for communication therefore compatible with:
- S7 300
- S7 400
- S7 1200 see Snap7 notes
- S7 1500 see Snap7 notes
- and compatible PLCs e.g. Yaskawa or VIPA
- uses PG-Communication (programming device communication) to connect the PLC
- optional also OP-Communication (HMI or panel communication) can be used for to connect the PLC
- NOTE: You may need to increase the connection resources for PG-Communication or OP-Communication within Siemens Simatic Manager or Siemens TIA Portal. The default value is 1 and thus lead to connection problems using programming tool or panel and this plugin at the same time.
- Tested with S7-300, S7-1200 and S7-300 compatible PLCs from Yaskawa
- Implementation is based on documentation of the Homebridge API
- Supports polling of PLC from homebridge-plc plugin by per accessory defined interval
- Supports push from PLC to homebridge-plc plugin by http PUT/GET
- Supports control of PLC accessories by http PUT/GET
- Supported Accessories:
- LightBulb as
PLC_LightBulb
- Outlet as
PLC_Outlet
- Switch as
PLC_Switch
- Temperature Sensor as
PLC_TemperatureSensor
- Humidity Sensor as
PLC_HumiditySensor
- Thermostat as
PLC_Thermostat
- Humidifier/Dehumidifier as
PLC_HumidifierDehumidifier
- Shutter as
PLC_WindowCovering
- Window as
PLC_Window
- Door as
PLC_Door
- Occupancy Sensor as
PLC_OccupancySensor
- Motion Sensor as
PLC_MotionSensor
- Contact Sensor as
PLC_ContactSensor
- Contact Sensor as
PLC_LeakSensor
- Faucet as
PLC_Faucet
- Valve as
PLC_Valve
- Security System as
PLC_SecuritySystem
- Push button attached to PLC as
PLC_StatelessProgrammableSwitch
- Doorbell push button attached to PLC as
PLC_Doorbell
- Lock mechanism as
PLC_LockMechanism
- Boolean lock mechanism as
PLC_LockMechanismBool
- Garage door as
PLC_GarageDoorOpener
- Smoke Sensor as
PLC_SmokeSensor
- Fan as
PLC_Fan
- Light Sensor as
PLC_LightSensor
- Air Purifier as
PLC_AirPurifier
- Filter Maintenance as
PLC_FilterMaintenance
- CarbonDioxideSensor as
PLC_CarbonDioxideSensor
- CarbonMonoxideSensor as
PLC_CarbonMonoxideSensor
- LightBulb as
Installation
Basic Installation
- Install this plugin using:
sudo npm install -g homebridge-plc
- Edit
config.json
to add the plc platform and its accessories. - Run Homebridge
- Install this plugin using:
Install via Homebridge UI (recommended)
- Search for
plc
on the plugin screen of config-ui-x . - Find
homebridge-plc
- Click install.
- Edit configuration
- Search for
Homebridge configuration
Platform
The plugin is configured as single platform by defining a PLC
platform.
Parameters:
ip
: the IPv4 address of the PLCrack
: the rack number of the PLC typically 0slot
: the slot number of the PLC for S7 300/400 typically2
, for 1200/1500 typically1
.communicationOP
: (optional) when set totrue
OP-Communication is used instead of PG-CommunicationenablePolling
: (optional) when set totrue
a background task is executed every second enable polling for the accessoriesdefaultPollInterval
(optional) default polling interval for all accessories in seconds. Default value is10
secondsdistributePolling
(optional) when set totrue
the polling of the accessories does not start at the same time. In order to distribute the PLC load for the queriesenablePush
: (optional) when set totrue
a the configuredport
is opened to push updates of values form plc to the pluginenableControl
: (optional) when set totrue
a the configuredport
is opened to control accessories by http requestport
: (optional) port for http server to handle incoming http requests for push and control functionality. Default port is8888
forward
: (optional) there is a limit of maximum 149 supported accessories by homebridge. To overcome this is limited you can create a second instance of homebridge running homebridge-plc and forward all push and control with no matchingdb
to the other instance. Set the destination address of the second instance e.g.http:\\127.0.0.1:8889
.mirror
(optional) There are environments where it could make sense to share the same accessories on two homebridge instances. To allow pairing with another Home with Apple Home App or Home Assistant. This option mirrors all values read from PLC by this instance to a second instance. It also forwards all push requests to the second instance. The optionenablePush
has to be enabled on the second instance. on the destination instance. Set the destination address of the second instance e.g.http:\\192.168.1.11:8888
. (expirimental feature)
Accessories
- In the platform, you can declare different types of accessories
- The notation (push support) identifies that parameter supports direct updates from the PLC
- The notation (control support) identifies parameters that can be controlled by http request
LightBulb as PLC_LightBulb
normal light see also simple PLC example for single bit and separate bits
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.get_On
: (push support) offset and bit get the current status S7 typeBool
e.g.55.0
forDB4DBX55.0
- Single Bit for on/off:
set_On
: (control support) offset and bit set to 1/0 when switching on/off S7 typeBool
PLC e.g.55.0
forDB4DBX55.0
could be same as get_On
- Separate Bits for on/off:
set_On
: (control support) offset and bit set to 1 when switching on S7 typeBool
PLC has to set to 0 e.g.55.1
forDB4DBX55.1
set_Off
: offset and bit set to 1 when switching off S7 typeBool
PLC has to set to 0 e.g.55.2
forDB4DBX55.2
get_Brightness
: (optional) (push support) get brightness value S7 typeByte
e.g.56
forDB4DBB56
set_Brightness
: (optional but required whenget_Brightness
is defined) (control support) set brightness value S7 typeByte
e.g.57
forDB4DBB57
- brightness range definitions (optional)
minBrightnessValue
default value: 0maxBrightnessValue
default value: 100minBrightnessStep
default value: 1
Outlet as PLC_Outlet
outlet possible to show also as ventilator or light
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.get_On
: (push support) offset and bit get the current status S7 typeBool
e.g.55.0
forDB4DBX55.0
- Single Bit for on/off:
set_On
: (control support) offset and bit set to 1/0 when switching on/off S7 typeBool
PLC e.g.55.0
forDB4DBX55.0
could be same as get_On
- Separate Bits for on/off:
set_On_Set
: (control support) offset and bit set to 1 when switching on S7 typeBool
PLC has to set to 0 e.g.55.1
forDB4DBX55.1
set_On_Reset
: offset and bit set to 1 when switching off S7 typeBool
PLC has to set to 0 e.g.55.2
forDB4DBX55.2
Switch as PLC_Switch
switch possible to show also as ventilator or light
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.get_On
: (push support) offset and bit get the current status S7 typeBool
e.g.55.0
forDB4DBX55.0
- Single Bit for on/off:
set_On
: (control support) offset and bit set to 1/0 when switching on/off S7 typeBool
PLC e.g.55.0
forDB4DBX55.0
could be same as get_On
- Separate Bits for on/off:
set_On
: (control support) offset and bit set to 1 when switching on S7 typeBool
PLC has to set to 0 e.g.55.1
forDB4DBX55.1
set_Off
: offset and bit set to 1 when switching off S7 typeBool
PLC has to set to 0 e.g.55.2
forDB4DBX55.2
Temperature Sensor as PLC_TemperatureSensor
normal temperature sensor
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.- Current Temperature
get_CurrentTemperature
: (push support) offset to get current temperature S7 typeReal
e.g.55
forDB4DBD55
- Temperature range (optional)
minTemperatureValue
default value: -270maxTemperatureValue
default value: 100minTemperatureStep
default value: 0.1
get_StatusTampered
: (optional) (push support) offset and bit to tamper detection. (Home app shows this only within the options) S7 typeBool
e.g.55.2
forDB4DBX55.2
false
: oktrue
: tampered
get_StatusLowBattery
: (optional) (push support) offset and bit to battery low detection. (Home app does not inform with push notification) S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: oktrue
: battery low
Humidity Sensor as PLC_HumiditySensor
normal humidity sensor
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.- Current Humidity
get_CurrentRelativeHumidity
: (push support) offset to get current humidity S7 typeReal
e.g.55
forDB4DBD55
- Humidity range (optional)
minHumidityValue
default value: 0maxHumidityValue
default value: 100minHumidityStep
default value: 1
get_StatusTampered
: (optional) (push support) offset and bit to tamper detection. (Home app shows this only within the options) S7 typeBool
e.g.55.2
forDB4DBX55.2
false
: oktrue
: tampered
get_StatusLowBattery
: (optional) (push support) offset and bit to battery low detection. (Home app does not inform with push notification) S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: oktrue
: battery low
Thermostat as PLC_Thermostat
temperature / humidity sensor with temperature / humidity regulation
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.- Current Temperature
get_CurrentTemperature
: (push support) offset to get current temperature S7 typeReal
e.g.0
forDB4DBD0
- Temperature range (optional)
minTemperatureValue
default value: -270maxTemperatureValue
default value: 100minTemperatureStep
default value: 0.1
- Target Temperature
get_TargetTemperature
: (push support) offset to get target temperature S7 typeReal
e.g.4
forDB4DBD4
set_TargetTemperature
: (control support) offset to set current temperature S7 typeReal
e.g.4
forDB4DBD4
(can have same value as get_TargetTemperature)- Target temperature range definitions (optional)
minTargetTemperatureValue
default value: 10maxTargetTemperatureValue
default value: 38minTargetTemperatureStep
default value: 0.1 Note: lower values seems not be supported by Homekit
- Current Humidity
get_CurrentRelativeHumidity
: (optional) (push support) offset to get current humidity S7 typeReal
e.g.0
forDB4DBD0
- Humidity range (optional)
minHumidityValue
default value: 0maxHumidityValue
default value: 100minHumidityStep
default value: 1
- Target Humidity
get_TargetRelativeHumidity
: (optional) (push support) offset to get target temperature S7 typeReal
e.g.4
forDB4DBD4
set_TargetRelativeHumidity
: (optional) (control support) offset to set current temperature S7 typeReal
e.g.4
forDB4DBD4
(can have same value as get_TargetTemperature)- Target relative humidity target range definitions (optional)
minTargetHumidityValue
default value: 0maxTargetHumidityValue
default value: 100minTargetHumidityStep
default value: 1
- Current State:
get_CurrentHeatingCoolingState
: (optional) (push support) offset to get current heating/cooling state S7 typeByte
e.g.8
forDB4DBB8
. When not defined fixed1
: heating is used.0
: inactive (shown as green in home app)1
: heating (shown as orange in home app)2
: cooling (shown as blue in home app)
mapGetCurrentHeatingCoolingState
: (optional) define mapping array forget_CurrentHeatingCoolingState
. The PLC value is used as index into the table. e.g.[0, 2]
which maps the PLC value0->0 1->2
when the PLC supports only two states with0:inactive
and1:cooling
.
- Target State:
get_TargetHeatingCoolingState
(optional) (push support) offset to get target heating/cooling state. S7 typeByte
e.g.9
forDB4DBB9
. When not defined fixed3
: automatic is used.0
: off1
: heat2
: cool3
: automatic
mapGetTargetHeatingCoolingState
: (optional) define mapping array forget_TargetHeatingCoolingState
. The PLC value is used as index into the table. e.g.[0, 3]
which maps the PLC value0->0 1->3
when the PLC supports only two states with0:off
and1:automatic
.set_TargetHeatingCoolingState
(optional) (control support) offset to set target heating/cooling state. Can be identical withget_TargetHeatingCoolingState
. Has to be defined whenget_TargetHeatingCoolingState
is defined. When not defined writes changes are ignored. S7 typeByte
e.g.9
forDB4DBB9
.0
: off1
: heat2
: cool3
: automatic
mapSetTargetHeatingCoolingState
: (optional) define mapping array forset_TargetHeatingCoolingState
. The home app value is used as index into the table. e.g.[0, 1, 0, 3]
which maps the PLC value0->0 1->1 2->0, 3->3
when the PLC supports only two states with0:off
and1:heat
and3:automatic
. The state cool is mapped to off.
get_StatusTampered
: (optional) (push support) offset and bit to tamper detection. (Home app shows this only within the options) S7 typeBool
e.g.55.2
forDB4DBX55.2
false
: oktrue
: tampered
get_StatusLowBattery
: (optional) (push support) offset and bit to battery low detection. (Home app does not inform with push notification) S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: oktrue
: battery low
Thermostat as PLC_HumidifierDehumidifier
Humidifier and/or Dehumidifier
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.get_CurrentRelativeHumidity
: (push support) offset to get current humidity S7 typeReal
e.g.55
forDB4DBD55
get_Active
: (push support) offset and bit get the current status S7 typeBool
e.g.55.0
forDB4DBX55.0
- Single Bit for on/off:
set_Active
: (control support) offset and bit set to 1/0 when switching on/off S7 typeBool
PLC e.g.55.0
forDB4DBX55.0
could be same as get_Active
- Separate Bits for on/off:
set_Active_Set
: (control support) offset and bit set to 1 when switching on S7 typeBool
PLC has to set to 0 e.g.55.1
forDB4DBX55.1
set_Active_Reset
: offset and bit set to 1 when switching off S7 typeBool
PLC has to set to 0 e.g.55.2
forDB4DBX55.2
- Current State
get_CurrentHumidifierDehumidifierState
: (optional) (push support) offset to get current state. Default value1:idle
. S7 typeByte
e.g.55
forDB4DBD55
0
: inactive1
: idle2
: humidifying3
: dehumidifying
mapGetCurrentHumidifierDehumidifierState
: (optional) define mapping array forget_CurrentHumidifierDehumidifierState
. The PLC value is used as index into the table. e.g.[1, 3]
which maps the PLC value0->1 1->3
when the PLC supports only two states with0:idle
and1:dehumidifying
.
- Target State
default_TargetHumidifierDehumidifierState
: (optional) defines alternative value thats returned thenget_TargetHumidifierDehumidifierState
is not defined. Default value0:auto
0
: auto (humidifier or dehumidifier)1
: humidifier2
: dehumidifier
get_TargetHumidifierDehumidifierState
: (optional) (push support) offset to get current target state S7 typeByte
e.g.55
forDB4DBD55
0
: auto (humidifier or dehumidifier)1
: humidifier2
: dehumidifier
set_TargetHumidifierDehumidifierState
: (optional) **(control support)**offset to set current target state. Needs to be defined whenget_TargetHumidifierDehumidifierState
is set S7 typeByte
e.g.55
forDB4DBD55
0
: auto (humidifier or dehumidifier)1
: humidifier2
: dehumidifier
mapGetTargetHumidifierDehumidifierState
: (optional) define mapping array forget_TargetHumidifierDehumidifierState
. The PLC value is used as index into the table. e.g.[2,1]
which maps the PLC value0->1 1->2
when the PLC supports only one states with `0:dehumidifier 1:humidifier.mapSetTargetHumidifierDehumidifierState
: (optional) define mapping array forset_TargetHumidifierDehumidifierState
. The home app value is used as index into the table. e.g. `[2, 2, 2] writes always the value 2 to the plc regardless whats set in the home app
- Rotation Speed
- Byte
get_RotationSpeedByte
: (optional) (push support) offset to get rotation speed state S7 typeByte
e.g.8
forDB4DBB8
.set_RotationSpeedByte
(optional but required whenset_RotationSpeedByte
is defined) (push support) offset to get set speed state. S7 typeByte
e.g.9
forDB4DBB9
.
- Real
get_RotationSpeed
: (optional) (push support) offset to get rotation speed state S7 typeReal
e.g.8
forDB4DBB8
.set_RotationSpeed
(optional but required whenget_RotationSpeed
is defined) (push support) offset to get set speed state. S7 typeReal
e.g.9
forDB4DBB9
.
- Byte
- Swing Mode
get_SwingMode
: (optional) (push support) offset to get swing mode. S7 typeByte
e.g.8
forDB4DBB8
.0
: swing disabled1
: swing enabled
set_SwingMode
(optional) (control support) offset to set swing mode. S7 typeByte
e.g.9
forDB4DBB9
.0
: swing disabled1
: swing enabled
- Water Level
get_WaterLevel
: (optional) (push support) offset to water level S7 typeReal
e.g.8
forDB4DBD8
.
get_StatusTampered
: (optional) (push support) offset and bit to tamper detection. (Home app shows this only within the options) S7 typeBool
e.g.55.2
forDB4DBX55.2
false
: oktrue
: tampered
get_StatusLowBattery
: (optional) (push support) offset and bit to battery low detection. (Home app does not inform with push notification) S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: oktrue
: battery low
Shutters as PLC_WindowCovering
, windows as PLC_Window
and doors as PLC_Door
motor driven blinds, windows and doors. Supports also manual driven blinds, windows and doors to show just the current position in percent. Note: If your sensor shows only open/close may also have a look at PLC_ContactSensor
.
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
adaptivePolling
: (optional) when set totrue
the current position will be polled until target position is reached. Polling starts with set target position from home app. This allows to show the shutter as opening... or closing... in the home app during movement.adaptivePollingInterval
(optional) poll interval in seconds during high frequency polling. Default value is1
second.forceCurrentPosition
(optional) when set totrue
the position set byset_TargetPosition
is directly used as current position. By this it seems in tha home app as the target position was directly reached. This is recommended when not usingadaptivePolling
or pushing the value from the plc.enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.- Current position:
get_CurrentPosition
: (push support) offset to get current position0:closed 100:open
S7 typeByte
e.g.0
forDB4DBB0
0
: closedin between
: partly open100
: open
invertPosition
: (optional) set totrue
to inverts the values of current and target position from0:closed 100:open
to100:closed 0:open
mapGetCurrentPosition
: (optional) define mapping array for get position. The PLC value is used as index into the table. e.g.[0, 25, 100]
which maps the PLC value0->0 1->25 2->100
this this is useful e.g. for window open state.
- Target position:
- if one of the (optional) target position settings need specified all are needed. If not specified it os not movable ans sticks to current position.
get_TargetPosition
: (optional) (push support) offset to get target position S7 typeByte
e.g.1
forDB4DBB1
(can have same value as set_TargetPosition)0
: closedin between
: partly open100
: open
set_TargetPosition
: (optional) (control support) offset to set current position0:closed 100:open
S7 typeByte
e.g.2
forDB4DBB2
(can have same value as get_TargetPosition)0
: closedin between
: partly open100
: open
get_PositionState
: (optional) (push support) offset to current movement state if not defined fixed2
is returned S7 typeByte
e.g.3
forDB4DBB3
0
: down1
: up2
: stop
set_HoldPosition
: (optional) (control support) offset and bit set to 1 to stop movement. (Seems not to be used by HomeApp) when not defined writes will be ignoredS7 typeBool
PLC has to set to 0 e.g.55.1
forDB4DBX55.1
Occupancy Sensor as PLC_OccupancySensor
presence detection sensor
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
invertOccupancy
: (optional) set totrue
inverts the bit tofalse:presence
andtrue:no-presence
.enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.get_OccupancyDetected
: (push support) offset and bit get the current status S7 typeBool
e.g.55.0
forDB4DBX55.0
false
: no occupancytrue
: occupancy detected
get_StatusTampered
: (optional) (push support) offset and bit to tamper detection. (Home app shows this only within the options) S7 typeBool
e.g.55.2
forDB4DBX55.2
false
: oktrue
: tampered
get_StatusLowBattery
: (optional) (push support) offset and bit to battery low detection. (Home app does not inform with push notification) S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: oktrue
: battery low
Motion Sensor as PLC_MotionSensor
movement detection sensor
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
invertMotionDetected
: (optional) set totrue
inverts the bit tofalse:motion
andtrue:no-motion
.enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.get_MotionDetected
: (push support) offset and bit get the current status S7 typeBool
e.g.55.0
forDB4DBX55.0
false
: no motiontrue
: motion detected
get_StatusTampered
: (optional) (push support) offset and bit to tamper detection. (Home app shows this only within the options) S7 typeBool
e.g.55.2
forDB4DBX55.2
false
: oktrue
: tampered
get_StatusLowBattery
: (optional) (push support) offset and bit to battery low detection. (Home app does not inform with push notification) S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: oktrue
: battery low
Contact Sensor as PLC_ContactSensor
generic contact sensor. The home app allows to display as window, door, blind/shutter, garage door or contact sensor.
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
invertContactSensorState
: (optional) set totrue
inverts the bit tofalse:closed
andtrue:open
.enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.get_ContactSensorState
: (push support) offset and bit get the current status S7 typeBool
e.g.55.0
forDB4DBX55.0
false
: closedtrue
: open
get_StatusTampered
: (optional) (push support) offset and bit to tamper detection. (Home app shows this only within the options) S7 typeBool
e.g.55.2
forDB4DBX55.2
false
: oktrue
: tampered
get_StatusLowBattery
: (optional) (push support) offset and bit to battery low detection. (Home app does not inform with push notification) S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: oktrue
: battery low
Contact Sensor as PLC_LeakSensor
leak sensor
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
invertLeakDetected
: (optional) set totrue
inverts the bit tofalse:leak detected
andtrue: no leak detected
.enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.get_LeakDetected
: (push support) offset and bit get the current status S7 typeBool
e.g.55.0
forDB4DBX55.0
false
: no leak detectedtrue
: leak detected
get_StatusTampered
: (optional) (push support) offset and bit to tamper detection. (Home app shows this only within the options) S7 typeBool
e.g.55.2
forDB4DBX55.2
false
: oktrue
: tampered
get_StatusLowBattery
: (optional) (push support) offset and bit to battery low detection. (Home app does not inform with push notification) S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: oktrue
: battery low
Faucet as PLC_Faucet
watering for the garden
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.get_Active
: (push support) offset and bit get the current status S7 typeBool
e.g.55.0
forDB4DBX55.0
- Single Bit for on/off:
set_Active
: (control support) offset and bit set to 1/0 when switching on/off S7 typeBool
PLC e.g.55.0
forDB4DBX55.0
could be same as get_Active
- Separate Bits for on/off:
set_Active
: (control support) offset and bit set to 1 when switching on S7 typeBool
PLC has to set to 0 e.g.55.1
forDB4DBX55.1
set_Deactivate
: offset and bit set to 1 when switching off S7 typeBool
PLC has to set to 0 e.g.55.2
forDB4DBX55.2
Valve as PLC_Valve
valve configurable as generic valve, irrigation, shower head or water faucet
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.ValveType
configures the valve type that is returned0
: generic valve1
: irrigation2
: shower head3
: water faucet
get_Active
: (push support) offset and bit get the current status S7 typeBool
e.g.55.0
forDB4DBX55.0
- Single Bit for on/off:
set_Active
: (control support) offset and bit set to 1/0 when switching on/off S7 typeBool
PLC e.g.55.0
forDB4DBX55.0
could be same as get_Active
- Separate Bits for on/off:
set_Active
: (control support) offset and bit set to 1 when switching on S7 typeBool
PLC has to set to 0 e.g.55.1
forDB4DBX55.1
set_Deactivate
: offset and bit set to 1 when switching off S7 typeBool
PLC has to set to 0 e.g.55.2
forDB4DBX55.2
- if one of the (optional) duration settings need specified all are needed
get_SetDuration
: (optional) (push support) offset to get duration 0..3600 sec S7 typeTime
e.g.10
forDB4DBD10
set_SetDuration
: (optional) (control support) offset to set duration 0..3600 sec S7 typeTime
e.g.14
forDB4DBD14
get_RemainingDuration
: (optional) (push support) offset to get remaining duration 0..3600 sec S7 typeTime
e.g.18
forDB4DBD18
Security System as PLC_SecuritySystem
:
alarm system
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state of the security system will be polled.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.- Current State:
get_SecuritySystemCurrentState
: (push support) offset to current security system state S7 typeByte
e.g.3
forDB4DBB3
0
: armed stay at home1
: armed away from home2
: armed night3
: disarmed4
: alarm triggered
mapGetSecuritySystemCurrentState
: (optional) define mapping array for get security system state. The PLC value is used as index into the table. e.g.[3, 1]
which maps the PLC value0->3 1->2
when the PLC supports only two states with0:disarmed
and1:armed
and2:alarm
.
- Target State:
set_SecuritySystemTargetState
: (control support) offset to set target security system state S7 typeByte
e.g.5
forDB4DBB4
get_SecuritySystemTargetState
: (push support) offset to set target security system state S7 typeByte
e.g.6
forDB4DBB6
0
: armed stay at home1
: armed away from home2
: armed night3
: disarmed
mapSetSecuritySystemTargetState
: (optional) define mapping array for set security system state. The home app value is used as index into the table. e.g.[1, 1, 1, 0, 2]
which maps the PLC value0->1 1->1 2->1, 3->0, 4->2
when the PLC supports only two states with0:disarmed
and1:armed
and2:alarm
.mapGetSecuritySystemTargetState
: (optional) define mapping array for get security system state. The PLC value is used as index into the table. e.g.[3, 1]
which maps the PLC value0->3 1->2
when the PLC supports only two states with0:disarmed
and1:armed
and2:alarm
.
Button as PLC_StatelessProgrammableSwitch
, Doorbell as PLC_Doorbell
stateless switch from PLC to home app.
Trigger actions in home app only works with control center e.g. AppleTV or HomePod. Polling or push from PLC required!
Polling mode homebridge-plc polls isEvent
. The PLC sets the bit to true
. hombebridge-plc reads get_ProgrammableSwitchEvent
and set the isEvent
bit to false
.
Push mode PLC informs homebridge-plc by http request with the value for get_ProgrammableSwitchEvent
.
Control External simulates event by http request with the value for get_ProgrammableSwitchEvent
.
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.isEvent
offset and bit that is polled by homebridge-plc. PLC has to set totrue
. Whentrue
the event is read fromget_ProgrammableSwitchEvent
and set tofalse
by homebirdge-plc to confirm that the event is handled. S7 typeBool
e.g.55.1
forDB4DBX55.1
(polling only, not used for push)get_ProgrammableSwitchEvent
: (push support) (control support) offset to read current event of the switch. This is reported towards home app S7 typeByte
e.g.3
forDB4DBB3
0
: single press1
: double press2
: long press
Lock mechanism as PLC_LockMechanism
lock mechanism
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.forceCurrentLockState
: (optional) when set totrue
the position set byset_LockTargetState
is directly used as current state. By this it seems in the home app as the target state was directly reached. This is recommended when not usingenablePolling
or pushing the value from the plc.get_LockCurrentState
: (push support) offset to read current state current state S7 typeByte
e.g.3
forDB4DBB3
0
: unsecured1
: secured2
: jammed3
: unknown
get_LockTargetState
: (push support) offset to read target state current state S7 typeByte
e.g.3
forDB4DBB3
0
: unsecured1
: secured
set_LockTargetState
: (control support) offset to write target state current state S7 typeByte
e.g.3
forDB4DBB3
0
: unsecured1
: secured
Boolean lock mechanism as PLC_LockMechanismBool
lock mechanism implemented as bool on the PLC
NOTE: The convention 0
=false
: closed/secured 1
=true
: open/unsecured
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. t is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.forceCurrentLockState
: (optional) when set totrue
the state set byset_LockTargetState
is directly used as current state. By this it seems in the home app as the target state was directly reached. This is recommended when not usingenablePolling
or pushing the value from the plc.invertLockState
: (optional) when set totrue
all states are inverted (current and target state)false
: unsecured andtrue
: secured.get_LockCurrentStateBool
: (push support) offset to read current state current state S7 typeBool
.g.3.1
forDB4DBB3
false
: securedtrue
: unsecured
get_LockTargetStateBool
: (push support) offset to read target state current state S7 typeBool
e..3.1
forDB4DBB3
false
: securedtrue
: unsecured
- Single Bit for secure/unsecured:
set_LockTargetStateBool
: (control support) offset to write target state current state S7 typeBool
e.g.3.1
forDB4DBB3
false
: securedtrue
: unsecured
- Separate Bits for secure/unsecured:
set_LockTargetStateBool_Secured
: (control support) offset and bit set totrue
when switching to target state secured S7 typeBool
PLC has to set tofalse
e.g.3.3
forDB4DBX55.1
set_LockTargetStateBool_Unsecured
: offset and bit set totrue
when switching to target state unsecured S7 typeBool
PLC has to set tofalse
e.g.3.4
forDB4DBX55.2
Garage door as PLC_GarageDoorOpener
garage door
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.forceCurrentDoorState
: (optional) when set totrue
the position set byset_TargetDoorState
is directly used as current state. By this it seems in the home app as the target state was directly reached. This is recommended when not usingenablePolling
or pushing the value from the plc.get_ObstructionDetected
(optional) (push support) offset and bit to obfuscation detection true means that the door was blocked S7 typeBool
e.g.55.1
forDB4DBX55.1
get_CurrentDoorState
: (push support) offset to read current state current state S7 typeByte
e.g.3
forDB4DBB3
0
: open1
: closed2
: opening3
: closing4
: stopped
get_TargetDoorState
: (push support) offset to read target state current state S7 typeByte
e.g.3
forDB4DBB3
0
: open1
: closed
set_TargetDoorState
: (control support) offset to write target state current state S7 typeByte
e.g.3
forDB4DBB3
0
: open1
: closed
Smoke Sensor as PLC_SmokeSensor
fire alarm
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.get_SmokeDetected
: (push support) offset and bit to smoke detection. S7 typeBool
e.g.55.1
forDB4DBX55.1
false
: oktrue
: smoke detected
get_StatusTampered
: (optional) (push support) offset and bit to tamper detection. (Home app shows this only within the options) S7 typeBool
e.g.55.2
forDB4DBX55.2
false
: oktrue
: tampered
get_StatusLowBattery
: (optional) (push support) offset and bit to battery low detection. (Home app does not inform with push notification) S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: oktrue
: battery low
Fan as PLC_Fan
ventilator
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.- Current State:
default_CurrentFanState
: (optional) defines alternative value thats returned thenget_CurrentFanState
is not defined. Default value `0:inactiveget_CurrentFanState
: (optional) (push support) offset to get current heating/cooling state S7 typeByte
e.g.8
forDB4DBB8
.0
: inactive1
: idle2
: blowing
mapCurrentFanStateGet
: (optional) define mapping array forget_CurrentFanState
. The PLC value is used as index into the table. e.g.[0, 2]
which maps the PLC value0->1 1->2
when the PLC supports only two states with0:idle
and1:blowing
.
- Target State:
default_TargetFanState
: (optional) defines alternative value thats returned thenget_TargetFanState
is not defined. Default value0:manual
0
: manual1
: automatic
get_TargetFanState
(optional) (push support) offset to get target heating/cooling state. S7 typeByte
e.g.9
forDB4DBB9
. When not defined fixed1
: automatic is used.0
: manual1
: automatic
set_TargetFanState
(optional but required whenget_TargetFanState
is defined) (control support) offset to get target heating/cooling state. S7 typeByte
e.g.9
forDB4DBB9
. When not defined fixed1
: automatic is used.0
: manual1
: automatic
mapTargetFanStateGet
: (optional) define mapping array forget_TargetFanState
. The PLC value is used as index into the table. e.g.[1, 0]
which maps the PLC value0->1 1->0
when the PLC supports only two states with0:automatic
and1:manual
.mapTargetFanStateSet
: (optional) define mapping array forset_TargetFanState
. The home app value is used as index into the table. e.g.[1, 0]
which maps the PLC value0->1 1->0
when the PLC supports only two states with0:automatic
and1:manual
.
- Rotation Direction
- get_RotationDirection (optional) (push support) offset to get rotation direction state. S7 type
Byte
e.g.9
forDB4DBB9
. When not defined fixed0
: clockwise is used.0
: clockwise1
: counter clockwise
- set_RotationDirection (optional) (control support) offset to set rotation directionstate. S7 type
Byte
e.g.9
forDB4DBB9
.0
: clockwise1
: counter clockwise
mapRotationDirectionGet
: (optional) define mapping array forget_RotationDirection
. The PLC value is used as index into the table. e.g.[1, 0]
inverts the direction.mapRotationDirectionSet
: (optional) define mapping array forset_RotationDirection
. The home app value is used as index into the table. e.g.[1, 0]
inverts the direction.
- get_RotationDirection (optional) (push support) offset to get rotation direction state. S7 type
- Rotation Speed
- Byte
get_RotationSpeedByte
: (optional) (push support) offset to get rotation speed state S7 typeByte
e.g.8
forDB4DBB8
.set_RotationSpeedByte
(optional but required whenset_RotationSpeedByte
is defined) (push support) offset to get set speed state. S7 typeByte
e.g.9
forDB4DBB9
.
- Real
get_RotationSpeed
: (optional) (push support) offset to get rotation speed state S7 typeReal
e.g.8
forDB4DBB8
.set_RotationSpeed
(optional but required whenget_RotationSpeed
is defined) (push support) offset to get set speed state. S7 typeReal
e.g.9
forDB4DBB9
.
- Byte
get_Active
: (push support) offset and bit get the current status S7 typeBool
e.g.55.0
forDB4DBX55.0
- Single Bit for on/off:
set_Active
: (control support) offset and bit set to 1/0 when switching on/off S7 typeBool
PLC e.g.55.0
forDB4DBX55.0
could be same as get_Active
- Separate Bits for on/off:
set_Active_Set
: (control support) offset and bit set to 1 when switching on S7 typeBool
PLC has to set to 0 e.g.55.1
forDB4DBX55.1
set_Active_Reset
: offset and bit set to 1 when switching off S7 typeBool
PLC has to set to 0 e.g.55.2
forDB4DBX55.2
Light Sensor as PLC_LightSensor
or PLC_LightSensor_DInt
Illuminance sensor
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.- AmbientLightLevel
- DInt
get_CurrentAmbientLightLevelDInt
: (push support) offset to get current illumination in LUX S7 typeDInt
value limited to 0.0001 ~ 100,000 e.g.55
forDB4DBD55
- Real
get_CurrentAmbientLightLevel
: (push support) offset to get current illumination in LUX S7 typeReal
value limited to 0.0001 ~ 100,000 e.g.55
forDB4DBD55
- DInt
get_StatusTampered
: (optional) (push support) offset and bit to tamper detection. (Home app shows this only within the options) S7 typeBool
e.g.55.2
forDB4DBX55.2
false
: oktrue
: tampered
get_StatusLowBattery
: (optional) (push support) offset and bit to battery low detection. (Home app does not inform with push notification) S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: oktrue
: battery low
Light Sensor as PLC_AirPurifier
Air filter
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.- Current State:
default_CurrentAirPurifierState
: (optional) defines alternative value thats returned thenget_CurrentAirPurifierState
is not defined. Default value `0:inactiveget_CurrentAirPurifierState
: (optional) (push support) offset to get current heating/cooling state S7 typeByte
e.g.8
forDB4DBB8
.0
: inactive1
: idle2
: purifying air
mapCurrentAirPurifierState
: (optional) define mapping array forget_CurrentAirPurifierState
. The PLC value is used as index into the table. e.g.[0, 2]
which maps the PLC value0->1 1->2
when the PLC supports only two states with0:inactive
and1:idle
.
- Target State:
default_TargetAirPurifierState
: (optional) defines alternative value thats returned thenget_TargetAirPurifierState
is not defined. Default value0:manual
0
: manual1
: automatic
get_TargetAirPurifierState
(optional) (push support) offset to get target heating/cooling state. S7 typeByte
e.g.9
forDB4DBB9
. When not defined fixed1
: automatic is used.0
: manual1
: automatic
set_TargetAirPurifierState
(optional but required whenget_TargetAirPurifierState
is defined) (control support) offset to get target heating/cooling state. S7 typeByte
e.g.9
forDB4DBB9
. When not defined fixed1
: automatic is used.0
: manual1
: automatic
mapTargetAirPurifierStateGet
: (optional) define mapping array forget_TargetAirPurifierState
. The PLC value is used as index into the table. e.g.[1, 0]
which maps the PLC value0->1 1->0
when the PLC supports only two states with0:automatic
and1:manual
.mapTargetAirPurifierStateSet
: (optional) define mapping array forset_TargetAirPurifierState
. The home app value is used as index into the table. e.g.[1, 0]
which maps the PLC value0->1 1->0
when the PLC supports only two states with0:automatic
and1:manual
.
- Swing Mode
get_SwingMode
: (optional) (push support) offset to get swing mode. S7 typeByte
e.g.8
forDB4DBB8
.0
: swing disabled1
: swing enabled
set_SwingMode
(optional) (control support) offset to set swing mode. S7 typeByte
e.g.9
forDB4DBB9
.0
: swing disabled1
: swing enabled
- Rotation Speed
- Byte
get_RotationSpeedByte
: (optional) (push support) offset to get rotation speed state S7 typeByte
e.g.8
forDB4DBB8
.set_RotationSpeedByte
(optional but required whenset_RotationSpeedByte
is defined) (push support) offset to get set speed state. S7 typeByte
e.g.9
forDB4DBB9
.
- Real
get_RotationSpeed
: (push support) offset to get rotation speed state S7 typeReal
e.g.8
forDB4DBB8
.set_RotationSpeed
(optional but required whenget_RotationSpeed
is defined) (push support) offset to get set speed state. S7 typeReal
e.g.9
forDB4DBB9
.
- Byte
get_Active
: (push support) offset and bit get the current status S7 typeBool
e.g.55.0
forDB4DBX55.0
- Single Bit for on/off:
set_Active
: (control support) offset and bit set to 1/0 when switching on/off S7 typeBool
PLC e.g.55.0
forDB4DBX55.0
could be same as get_Active
- Separate Bits for on/off:
set_Active_Set
: (control support) offset and bit set to 1 when switching on S7 typeBool
PLC has to set to 0 e.g.55.1
forDB4DBX55.1
set_Active_Reset
: offset and bit set to 1 when switching off S7 typeBool
PLC has to set to 0 e.g.55.2
forDB4DBX55.2
- Filter change
get_FilterChangeIndication
: (push support) offset and bit to filter change indication S7 typeBool
e.g.55.3
forDB4DBX55.3
0
: filter oktrue
: change filter
get_FilterLifeLevel
: (optional) (push support) offset and bit to filter live level S7 typeByte
e.g.56
forDB4DBX56
0
: change filter100
: filter is new
set_ResetFilterIndication
: (optional) (control support) offset and bit to filter change indication S7 typeBool
PLC has to set to 0 after detecting change to true via homebridge e.g.55.4
forDB4DBX55.4
NOTE: Currently not used by HomeApp
Filter mainanance indicator as PLC_FilterMaintenance
Filter change indication (Currently neither supported in HomeApp and HomeBridge)
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.- Filter change
get_FilterChangeIndication
: (push support) offset and bit to filter change indication S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: filter oktrue
: change filter
get_FilterLifeLevel
: (optional) (push support) offset and bit to filter live level S7 typeByte
e.g.56
forDB4DBX56
0
: change filter100
: filter is new
set_ResetFilterIndication
: (optional) (control support) offset and bit to filter change indication S7 typeBool
PLC has to set to 0 after detecting change to true via homebridge e.g.55.4
forDB4DBX55.4
NOTE: Currently not used by HomeApp
C02 Sensor as PLC_CarbonDioxideSensor
Carbon Dioxide Sensor
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.- Detected
get_CarbonDioxideDetected
: (push support) offset and bit for CO2 detection S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: normal CO2 leveltrue
: abnormal CO2 level
get_StatusTampered
: (optional) (push support) offset and bit to tamper detection. (Home app shows this only within the options) S7 typeBool
e.g.55.2
forDB4DBX55.2
false
: oktrue
: tampered
get_StatusLowBattery
: (optional) (push support) offset and bit to battery low detection. (Home app does not inform with push notification) S7 typeBool
e.g.55.3
for
C0 Sensor as PLC_CarbonMonoxideSensor
Carbon Monoxid Sensor
name
: unique name of the accessorymanufacturer
: (optional) descriptiondb
: s7 data base number e.g.4
forDB4
enablePolling
: (optional) when set totrue
the current state will be polled. It is mandatory as well to enable polling mode on platform level.pollInterval
: (optional) poll interval in seconds. Default value see platform definition.- Detected
get_CarbonMonoxideDetected
: (push support) offset and bit for CO detection S7 typeBool
e.g.55.3
forDB4DBX55.3
false
: normal CO leveltrue
: abnormal CO level
get_StatusTampered
: (optional) (push support) offset and bit to tamper detection. (Home app shows this only within the options) S7 typeBool
e.g.55.2
forDB4DBX55.2
false
: oktrue
: tampered
get_StatusLowBattery
: (optional) (push support) offset and bit to battery low detection. (Home app does not inform with push notification) S7 typeBool
e.g.55.3
for
config.json Example
Note: The example is just an example it contains also some optional settings. For testing purposes all accessories are set to one DB.
{
"bridge": {
"name": "Homebridge DEMO",
"username": "0E:54:47:36:82:26",
"port": 52609,
"pin": "031-55-155"
},
"accessories": [],
"platforms": [
{
"name": "Config",
"port": 8888,
"platform": "config"
},
{
"platform": "PLC",
"ip": "10.10.10.32",
"rack": 0,
"slot": 2,
"communicationOP": false,
"enablePolling": true,
"defaultPollInterval": 15,
"distributePolling": true,
"enablePush": true,
"enableControl": true,
"port": 8888,
"accessories": [
{
"accessory": "PLC_LightBulb",
"name": "LightBulb0",
"manufacturer": "normal light bulb",
"enablePolling": true,
"db": 12,
"get_On": 0.0,
"set_On": 0.1,
"set_Off": 0.2
},
{
"accessory": "PLC_LightBulb",
"name": "LightBulb1",
"manufacturer": "with dim function",
"enablePolling": true,
"db": 12,
"get_On": 2.0,
"set_On": 2.1,
"set_Off": 2.2,
"get_Brightness": 1,
"set_Brightness": 1
},
{
"accessory": "PLC_LightBulb",
"name": "LightBulb2",
"manufacturer": "single bit for on/off",
"enablePolling": true,
"db": 12,
"get_On": 2.3,
"set_On": 2.3
},
{
"accessory": "PLC_Outlet",
"name": "Outlet",
"enablePolling": true,
"db": 12,
"get_On": 2.4,
"set_On": 2.5
},
{
"accessory": "PLC_Switch",
"name": "Switch",
"enablePolling": true,
"db": 12,
"get_On": 2.6,
"set_On": 2.7,
"set_Off": 3.0
},
{
"accessory": "PLC_TemperatureSensor",
"name": "Temperature",
"db": 12,
"get_CurrentTemperature": 4,
"enablePolling": true,
"pollInterval": 60
},
{
"accessory": "PLC_HumiditySensor",
"name": "Humidity",
"db": 12,
"get_CurrentRelativeHumidity": 8,
"enablePolling": true,
"pollInterval": 120
},
{
"accessory": "PLC_Thermostat",
"name": "Thermostat",
"manufacturer": "ground floor",
"db": 12,
"enablePolling": true,
"get_CurrentTemperature": 12,
"get_TargetTemperature": 16,
"set_TargetTemperature": 16,
"get_CurrentHeatingCoolingState": 20
"mapSetTargetHeatingCoolingState": [
0,
1,
0,
3
],
},
{
"accessory": "PLC_WindowCovering",
"name": "Blind",
"manufacturer": "ground floor",
"db": 12,
"invertPosition": false,
"adaptivePolling": true,
"adaptivePollingInterval": 1,
"enablePolling": true,
"pollInterval": 180,
"get_CurrentPosition": 21,
"get_TargetPosition": 22,
"set_TargetPosition": 1
},
{
"accessory": "PLC_Window",
"name": "Window",
"manufacturer": "ground floor",
"enablePolling": true,
"pollInterval": 60,
"db": 12,
"get_CurrentPosition": 23,
"mapGetCurrentPosition": [
0,
25,
100
]
},
{
"accessory": "PLC_Door",
"name": "Door",
"manufacturer": "ground floor",
"enablePolling": true,
"pollInterval": 10,
"db": 12,
"get_CurrentPosition": 24,
"mapGetCurrentPosition": [
0,
100
]
},
{
"accessory": "PLC_OccupancySensor",
"name": "Presence",
"enablePolling": true,
"db": 12,
"get_OccupancyDetected": 25.0
},
{
"accessory": "PLC_MotionSensor",
"name": "Motion",
"enablePolling": true,
"db": 12,
"get_MotionDetected": 25.1
},
{
"accessory": "PLC_ContactSensor",
"name": "ContactSensor",
"enablePolling": true,
"pollInterval": 5,
"db": 12,
"get_ContactSensorState": 25.2
},
{
"accessory": "PLC_LeakSensor",
"name": "LeakSensor",
"enablePolling": true
"pollInterval": 5,
"db": 12,
"get_LeakDetected": 25.3,
},
{
"accessory": "PLC_Faucet",
"name": "Faucet",
"enablePolling": true,
"db": 12,
"get_Active": 28.0,
"set_Active": 28.0
},
{
"accessory": "PLC_Valve",
"name": "Valve",
"db": 12,
"enablePolling": true,
"ValveType": 2,
"get_Active": 28.1,
"set_Active": 28.1,
"get_SetDuration": 30,
"set_SetDuration": 30,
"get_RemainingDuration": 34
},
{
"accessory": "PLC_SecuritySystem",
"name": "SecuritySystem",
"db": 12,
"enablePolling": true,
"pollInterval": 60,
"get_SecuritySystemCurrentState": 26,
"set_SecuritySystemTargetState": 27,
"get_SecuritySystemTargetState": 27,
"mapGetSecuritySystemCurrentState": [
3,
1,
4
],
"mapGetSecuritySystemTargetState": [
3,
1
]
"mapSetSecuritySystemTargetState": [
1,
1,
1,
0
]
},
{
"accessory": "PLC_StatelessProgrammableSwitch",
"name": "Stateless Switch",
"enablePolling": true,
"pollInterval": 10,
"db": 12,
"isEvent": 29.2,
"get_ProgrammableSwitchEvent": 38
},
{
"accessory": "PLC_Doorbell",
"name": "Doorbell",
"enablePolling": true,
"pollInterval": 10,
"db": 12,
"isEvent":